You can also find us on the following platforms↓
Home » Filter Knowledge Center » Products News » HVAC Filters » Air Filter Classification Guide: MERV, ISO 16890, EN 1822 and China GB Standards

Air Filter Classification Guide: MERV, ISO 16890, EN 1822 and China GB Standards

Views: 0     Author: Site Editor     Publish Time: 2021-12-18      Origin: Site

Inquire

facebook sharing button
twitter sharing button
line sharing button
wechat sharing button
linkedin sharing button
pinterest sharing button
whatsapp sharing button
sharethis sharing button


AIR FILTER CLASSIFICATION GUIDE: MERV, ISO 16890, EN 1822 and China GB Standards

Air filter classification systems help engineers, HVAC contractors, facility managers and buyers compare filtration performance against defined test methods. However, the United States, Europe and China use different standards, particle-size ranges and rating rules. A filter labeled MERV 13, ISO ePM1 60% or H13 should therefore not be assumed to have an interchangeable rating.

This guide explains the main classification systems used for general ventilation and high-efficiency air filters: ANSI/ASHRAE 52.2 in the United States, ISO 16890 and EN 1822 in Europe, and GB/T 14295 and GB/T 13554 in China. It also explains why ratings from different systems cannot be converted directly.


1. United States: ANSI/ASHRAE 52.2 and MERV


The United States commonly uses the Minimum Efficiency Reporting Value (MERV) system under ANSI/ASHRAE Standard 52.2. The standard evaluates the particle-removal performance of general ventilation air-cleaning devices by particle size and also measures resistance to airflow. The current edition is ANSI/ASHRAE 52.2-2025.

The test evaluates particles in three size ranges: E1 (0.30–1.0 μm), E2 (1.0–3.0 μm) and E3 (3.0–10.0 μm). MERV ratings range from 1 to 16. A higher MERV rating generally indicates higher particle-removal efficiency under the standard test conditions.



MERV classification under ANSI/ASHRAE 52.2
MERV Rating

E1

0.30–1.0 μm

E2

1.0–3.0 μm

E3

3.0–10.0 μm

Additional criterion
MERV1 - - <20% Average arrestance <65%
MERV2 - - <20% 65% ≤ arrestance <70%
MERV3 - - <20% 70% ≤ arrestance <75%
MERV4 - - <20% Arrestance ≥75%
MERV5 - - ≥20% -
MERV6 - - ≥35% -
MERV7 - - ≥50% -
MERV8 - ≥20% ≥70% -
MERV9 - ≥35% ≥75% -
MERV10 - ≥50% ≥80% -
MERV11 ≥20% ≥65% ≥85% -
MERV12 ≥35% ≥80% ≥90% -
MERV13 ≥50% ≥85%
≥90% -
MERV14 ≥75% ≥90% ≥95% -
MERV15 ≥85% ≥90% ≥95% -
MERV16 ≥95% ≥95% ≥95% -



How to read the table: The E1, E2 and E3 values are minimum efficiency thresholds for the applicable size ranges. A dash means that the size range is not used as a rating threshold for that MERV level; it does not mean zero filtration. MERV 1–4 are distinguished using average arrestance as shown in the final column.

 

2. Europe: General Ventilation Filters under ISO 16890


ISO 16890 classifies air filters for general ventilation according to their particulate matter efficiency (ePM). It replaced the former EN 779 classification system for general ventilation filters. The four main groups are ISO Coarse, ISO ePM10, ISO ePM2.5 and ISO ePM1.

As of November 26, 2026, ISO 16890-1:2016 remains the published edition shown as current on the ISO catalogue. The second edition, ISO 16890-1:2026, is in the final publication process and is expected to replace the 2016 edition. Check the ISO catalogue before publishing a later revision of this article.



General ventilation filter groups under ISO 16890
Filter Group Classification Threshold Reported Class Value Example of Class Marking
ISO Coarse Initial gravimetric arrestance <50% Initial gravimetric arrestance ISO Coarse 60%
ISO ePM10 ePM10 ≥50% ePM10 efficiency ISO ePM10 60%
ISO ePM2.5 ePM2.5,min ≥50% ePM2.5 efficiency ISO ePM2.5 80%
ISO ePM1 ePM1,min ≥50% ePM1 efficiency

ISO ePM1 85%

3. Europe: EPA, HEPA and ULPA Filters under EN 1822


EN 1822-1:2019 classifies high-efficiency air filters into EPA, HEPA and ULPA groups. Classification is based on filtration efficiency at the most penetrating particle size (MPPS), rather than on a single fixed particle size such as 0.3 μm.

For Group E filters (E10–E12), classification is based on integral efficiency. For Group H (H13–H14) and Group U (U15–U17), both integral and local efficiency requirements apply.



EPA, HEPA and ULPA classification under EN 1822-1:2019
Filter Group Class Integral Efficiency at MPPS Local Efficiency at MPPS Reference
EPA E10 ≥85% - -
EPA E11 ≥95% - -
EPA E12 ≥99.5% - -
HEPA H13 ≥99.95% ≥99.75% ≤0.05% overall penetration
HEPA H14 ≥99.995%
≥99.975% ≤0.005% overall penetration
ULPA U15 ≥99.9995% ≥99.9975% ≤0.0005% overall penetration
ULPA U16 ≥99.99995% ≥99.99975% ≤0.00005% overall penetration
ULPA U17 ≥99.999995% ≥99.9999%

≤0.000005% overall

 penetration

4. China: General Ventilation Filters under GB/T 14295-2019

GB/T 14295-2019, Air Filters, applies to filters used in ventilation, air-conditioning and air-purification systems or equipment. It covers coarse, medium, medium-high and sub-high efficiency filters, but it does not apply to high-efficiency filters and above.

The standard uses different test methods for different classes. C1 and C2 are classified by gravimetric efficiency using standard test dust. C3 and C4 use particle-counting efficiency for particles ≥2.0 μm. Z1, Z2, Z3, GZ and YG use particle-counting efficiency for particles ≥0.5 μm.

General ventilation filter classes under GB/T 14295-2019
Filter Category Class Code Test Basis Efficiency Range
Coarse 1 C1       Standard test dust, gravimetric efficiency             20% ≤ E <50%
Coarse 2 C2 Standard test dust, gravimetric efficiency E ≥50%
Coarse 3 C3 Particle-counting efficiency, particle size ≥2.0 μm 10% ≤ E <50%
Coarse 4 C4 Particle-counting efficiency, particle size ≥2.0 μm E ≥50%
Medium 1 Z1 Particle-counting efficiency, particle size ≥0.5 μm 20% ≤ E <40%
Medium2 Z2 Particle-counting efficiency, particle size ≥0.5 μm 40% ≤ E <60%
Medium 3 Z3 Particle-counting efficiency, particle size ≥0.5 μm 60% ≤ E <70%
Medium-high GZ Particle-counting efficiency, particle size ≥0.5 μm 70% ≤ E <95%
Sub-high YG Particle-counting efficiency, particle size ≥0.5 μm 95% ≤ E <99.9%

5. China: HEPA and ULPA Filters under GB/T 13554-2020

GB/T 13554-2020, High Efficiency Particulate Air Filter, covers high-efficiency and ultra-high-efficiency filters used in supply-air and exhaust-air purification systems under normal-temperature conditions. It divides high-efficiency filters into classes 35, 40 and 45, and ultra-high-efficiency filters into classes 50, 55, 60, 65, 70 and 75.


High-efficiency and ultra-high-efficiency filter classes under GB/T 13554-2020
Filter Category Efficiency Class Efficiency at Rated Airflow
High-efficiency filter 35 ≥99.95%
High-efficiency filter 40 ≥99.99%
High-efficiency filter 45 ≥99.995%
Ultra-high-efficiency filter 50 ≥99.999%
Ultra-high-efficiency filter 55 ≥99.9995%
Ultra-high-efficiency filter 60 ≥99.9999%
Ultra-high-efficiency filter 65 ≥99.99995%
Ultra-high-efficiency filter 70 ≥99.99999%
Ultra-high-efficiency filter 75 ≥99.999995%

6. Can MERV, ISO, EN and GB Ratings Be Converted Directly?


No. The rating systems are based on different test procedures, particle-size definitions, conditioning steps, airflow conditions and classification rules. A percentage printed beside two different class names is not enough to establish equivalence.

  • MERV is determined using the particle-size efficiency and arrestance requirements of ANSI/ASHRAE 52.2.

  • ISO 16890 reports particulate matter efficiency groups and uses a prescribed conditioning procedure for minimum efficiency assessment.

  • EN 1822 classifies EPA, HEPA and ULPA filters using MPPS efficiency, and applies local-efficiency and leak-testing requirements to H and U groups.

  • GB/T 14295 and GB/T 13554 use Chinese national test procedures and class definitions that should be quoted together with the relevant standard and test method.



7. How to Select a Filter for an HVAC or Industrial Application

A suitable filter should be selected by considering the complete operating conditions, not by choosing the highest available efficiency rating.

  1. Confirm the application: fresh-air intake, return air, process ventilation, cleanroom supply, paint booth, dust collection or another use.

  2. Confirm the required standard and market: ASHRAE/MERV for many U.S. HVAC specifications, ISO 16890 for general ventilation in many international and European projects, EN 1822 or ISO 29463 for high-efficiency filtration, and the applicable GB standards for projects requiring Chinese national standards.

  3. Confirm the rated airflow and face velocity. The test rating must be relevant to the intended operating point.

  4. Check initial pressure drop and the system fan's available static pressure. A higher-efficiency filter may increase resistance and reduce airflow if the system is not designed for it.

  5. Check dimensions, frame material, gasket or gel seal, installation direction, temperature, humidity, chemical exposure and fire-performance requirements.

  6. Request a current test report showing the standard edition, class, test method, airflow, efficiency, pressure drop and leak-test results where required.

For bag filters, mini-pleat filters, V-bank filters and HEPA terminal filters, the correct choice depends on the system design, target cleanliness, airflow, available installation space and total operating cost. Efficiency should be balanced with pressure drop, dust-holding capacity and service life.


8. Frequently Asked Questions

1. What is the difference between MERV and HEPA?

MERV is a rating system for general-ventilation air-cleaning devices under ASHRAE 52.2. HEPA is a high-efficiency filter category assessed under separate standards such as EN 1822 or ISO 29463. A HEPA filter should not be described simply as a MERV 17 or MERV 20 filter.


2. Has EN 779 been replaced?

For general ventilation filters, EN 779 has been superseded by the ISO 16890 classification framework. G1–G4 and F5–F9 should be identified as legacy EN 779 classes, not current ISO 16890 classes.


3. What is the difference between H13 and H14?

Under EN 1822-1:2019, H13 has an integral MPPS efficiency of at least 99.95% and a local efficiency of at least 99.75%. H14 has an integral efficiency of at least 99.995% and a local efficiency of at least 99.975%. Both classes have leak-testing requirements.


4. Is MERV 13 equal to ISO ePM1 50%?

No. The two systems use different test procedures and classification rules. Any comparison should be treated as approximate only when supported by suitable test data; it is not a formal one-to-one conversion.


5. Is GB/T 13554 class 35 the same as H13?

No. Their integral efficiency thresholds are numerically similar, but the standards use different test and classification requirements. Specify the actual standard and class shown on the test report.


6. Can ISO 16890 be used for portable air purifier filters?

ISO 16890-1 excludes filter elements used in portable room-air cleaners. Select an applicable test method and product standard for the specific air-cleaner application.


Conclusion

MERV, ISO 16890, EN 1822 and China GB standards each serve a different classification purpose. MERV and ISO 16890 are widely used for general ventilation filters, while EN 1822 and GB/T 13554 provide classification frameworks for high-efficiency and ultra-high-efficiency filters. Correct product selection requires more than comparing efficiency percentages: the test standard, particle-size basis, airflow, pressure drop, filter construction and leakage requirements must all be considered.

Need help selecting the right air filter for your HVAC or industrial filtration application? Contact Nanjing Blue Sky Filter with your required airflow, filter dimensions, target efficiency, operating conditions and project requirements. Our team can help evaluate suitable filtration solutions and OEM/ODM options.

Please feel free to send your inquiry to sales@bluesky-filter.com.


Banner

Nanjing Blue Sky Filter Provides Customized Services


If you want to see our updates in real time on social media, you can follow the following accounts.

LinkedIn: linkedin.com/company/blueskyfilter

Twitter: twitter.com/blueskyfilter

Facebook: www.facebook.com/blueskyfilter.manufacturer/
Youtube: www.youtube.com/@blueskyfilter
Instagram: https://www.instagram.com/nanjingblueskyfilters/



Related Products

Leave a Message
Contact Us
Please feel free to send your designs and samples for our company to cooperate with you!
Subscribe

Contact Us

More >>
  LISHUI ECONOMIC DEVELOPMENT ZONE,NANJING
  +86-25-58071605
  bsfilter8@bluesky-filter.com
  sales@bluesky-filter.com

According to the Properties and Shapes

According to the Use

Copyright  2017 NANJING BLUE SKY FILTER CO.,LTD.   All rights reserved.  苏ICP备2024088838号