| United States Efficiency Specification | ||||||
| Specification | Particle Efficiency(%) | Arrestance(%) | TEST | |||
| Arrestance | The End Resistance(Pa) | |||||
| Final Resist | ||||||
| 0.3~1.0μm | 1.0~3.0μm | 3.0~10.0μm | ||||
| MERV1 | E3<20 | Aavg<65 | 75 | E1 is 0.30-0.40,0.40-0.55,0.55-0.70,0.70-1.0μm four particle size interval of the whole process of the test the lowest average; E2 is 1.0 to 1.3, 1.3-1.6, 1.6-2.2, 2.2 to 3.0 mu m four the minimum average particle size range; E3 is 4.0 to 4.0, 4.0-5.5, 5.5-7.0, 7.0 to 10.0 mu m four lowest average particle size range | ||
| MERV2 | E3<20 | 65≤Aavg<70 | 75 | |||
| MERV3 | E3<20 | 70≤Aavg<75 | 75 | |||
| MERV4 | E3<20 | 70≤Aavg | 75 | |||
| MERV5 | 20≤E3<35 | 150 | ||||
| MERV6 | 35≤E3<50 | 150 | ||||
| MERV7 | 50≤E3<70 | 150 | ||||
| MERV8 | 70≤E3<80 | 150 | ||||
| MERV9 | E2<50 | 85≤E3 | 250 | |||
| MERV10 | 50≤E2<65 | 85≤E3 | 250 | |||
| MERV11 | 65≤E2<80 | 85≤E3 | 250 | |||
| MERV12 | 80≤E2<90 | 90≤E3 | 250 | |||
| MERV13 | E1<75 | 90≤E2 | 90≤E3 | 350 | ||
| MERV14 | 75≤E1<75 | 90≤E2 | 90≤E3 | 350 | ||
| MERV15 | 85≤E1<95 | 90≤E2 | 90≤E3 | 350 | ||
| MERV16 | 95≤E1 | 95≤E2 | 95≤E3 | 350 | ||
| MERV17 | ≥99.97% IEST-Class A | |||||
| MERV18 | For 0.3 μm Particle ≥99.99% IEST-Class C HEPA Filter | |||||
| MERV19 | ≥99.999% IEST-Class D | |||||
| MERV20 | For 0.1~0.2μm Particle, Scanning Method≥99.999% IEST-Class F UEPA Filter | |||||
| Current Classification in Europe | |||
| Standard | EN779:1993 | EN1882-1:1998 | |
| Specification | Proportion Method(%) | Colorimetric or Counting Methods(%) | Most Permeable Particle Size Method(%) |
| Arrestance | Dust-spot | MPPS | |
| Or Particle Efficiency | |||
| G1 | E<65 | ||
| G2 | 65≤E<80 | ||
| G3 | 80≤E<90 | ||
| G4 | 90≤E | ||
| F5 | 40≤E<60 | ||
| F6 | 60≤E<80 | ||
| F7 | 80≤E<90 | ||
| F8 | 90≤E<95 | ||
| F9 | 95≤E | ||
| H10 | 85≤E<95 | ||
| H11 | 95≤E<99.5 | ||
| H12 | 99.5≤E<99.95 | ||
| H13 | 99.95≤E<99.995 | ||
| H14 | 99.995≤E<99.9995 | ||
| U15 | 99.9995≤E<99.99995 | ||
| U16 | 99.99995≤E<99.999995 | ||
| U17 | 99.999995≤E | ||
| Classification of air filtration (GB) | |||||
| GB12218-89 Classification | I | Ⅱ | Ⅲ | Ⅳ | Ⅴ |
| Partical Size(μm) | ≥5.0 | ≥1.0 | ≥0.5 | ||
| Counting Efficiency( %) | <40 | 40<E<80 | 40<E<80 | 70<E<99 | 95<E<99.9 |
| GB/T14295-93 Classification | Coarse Effect | Intermediate-acting | High Efficiency | Sub HEPA | |
| Particle Size (μm) | ≥5.0 | ≥1.0 | ≥0.5 | ||
| Counting Efficiency(%) | 20<E<80 | 20<E<70 | 70<E<99 | 95<E<99.9 | |
Breathe Fresh for The Elderly – Celebrate Double Ninth Festival with Cleaner Air at Home
Breathe Easy This Autumn – Upgrade Your HVAC and Industrial Filters for Better Air Quality
Your Trusted Partner for HVAC and Industrial Air Filtration Solutions
Keep Your Cool This Summer: Why Cleaning Your AC and HVAC Filters Matters
The Importance of Replacing HVAC Filter Element Regularly in Winter
HVAC Filters Appliances' Filter Replacements Automobile Filter Replacements True HEPA Filters Bag Filters Pre-Filters